XQ330 Tier 4 Final

XQ330 Tier 4 Final (264 ekW, 330 kVA)

XQ330 Tier 4 Final

The Cat® XQ330 provides world class performance and enhanced usability. This model is powered by the fuel-efficient Cat C9.3 Tier 4 Final compliant engine equipped with the Cat NOx Reduction System. Equipped with the EMCP 4.4 control panel, the XQ330 features a user-friendly interface and automatic generator set paralleling. A principle advantage of the control system offers simpler and faster voltage changes. Providing greater flexibility when moving between multiple job sites with differing frequency and voltage needs, the auto-configuration capability eliminates the time required when reprogramming units and potential errors. Additional features include lower noise levels and improved part load fuel consumption.
Electric Power

Rating Prime

264 eKW (330 kVA)

Frequency

50/60 Hz

Voltage

120 - 600 V
  • Specifications
  • Standard / Optional Features
  • Overview
    • Long Name -XQ330 Tier 4 Final (264 ekW, 330 kVA)
    • Name -XQ330 Tier 4 Final
    • Brand -Cat
    • Status -Current
  • Generator Set
    • Rating Prime - 264 eKW (330 kVA)
    • Frequency - 50/60 Hz
    • Voltage - 120 - 600 V
    • Rating Standby - 288 ekW (360 kVA)
  • Engine
    • Engine - C9.3B
    • Fuel - Diesel
  • Dimensions
    • Height - Without Trailer - 78.5 in / 1994 mm
    • Length - Without Trailer - 162.2 in / 4120 mm
    • Width - Without Trailer - 92.8 in / 1595 mm
    • Weight with Lube Oil and Coolant, Without Trailer - 10405 lb / 4720 kg
  • Fuel Consumption
    • 100% Load 60 Hz - 18.5 gal/hr / 70 l/hr
    • 75% Load 60 Hz - 13.7 gal/hr / 52 l/hr
    • 50% Load 60Hz - 9.8 gal/hr / 37 l/hr
    • 100% Load 50 Hz - 16.5 gal/hr / 62.5 l/hr
    • 75% Load 50 Hz - 12.5 gal/hr / 47.3 l/hr
  • Noise rating (with enclosure)
    • Sound Power @ 7 meters (23 feet) @ Prime Rating - 70.2 dB(A) (60Hz)
  • Standard Equipment

    • cat c9.3b diesel engine
      • Heavy-duty.
        Turbocharged.
        After treatment
    • generator
      • LC5134N Frame
    • control panel
      • Digital EMCP4.4 set mounted controller
    • cat connect remote monitoring
      • Provides package monitoring and management
    • cooling system
      • Package mounted radiator with vertical air discharge.
        Filled from factory
    • charging / starting system
      • Single 24V electric starting motor
    • fuel system
      • 24 hour dual wall fuel tank
    • air filter
      • Efficient air cleaner with service indicator
    • distribution
      • Single, robust enclosure for controls and distribution c/w 3 pole 1000A maim circuit breaker and safety cut off
    • structure
      • Heavy Duty steel base frame with integral fuel tank.
        Dual Point Lifting frame and 4 point lift.
        base frame is wider than enclosure to protect generator set during transportation
    • enclosure
      • Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance
    • exhaust
      • Integrated spark arresting silencer
    • lube oil
      • On engine primary and secondary oil filters. Filled from factory 500-hour oil change interval
    • general
      • Factory tested and inspected