XQ125 Tier 4 Final

XQ125 Rental Power

With a robust, rental-ready construction, the 100 kW (125 kVA) XQ125 generator is designed to be easily transported around project sites safely and efficiently.

XQ125 Tier 4 Final

The Cat XQ125 is powered by a C 4.4 Tier 4 Final compliant industrial diesel engine offering the perfect balance of durability, efficiency and low emissions. With advanced research and development techniques, the after treatment system is precisely matched to the engine ensuring performance is optimized for maximum productivity.
Electric Power

Rating Prime

100 ekW (125 kVA)

Frequency

60 Hz

Voltage

120 - 600 V
  • Specifications
  • Standard / Optional Features
  • Overview
    • Long Name -XQ125 Rental Power
    • Name -XQ125 Tier 4 Final
    • Brand -Caterpillar
    • Status -Current
  • Generator Set
    • Rating Prime - 100 ekW (125 kVA)
    • Frequency - 60 Hz
    • Voltage - 120 - 600 V
  • Engine
    • Engine - Cat C4.4
    • Fuel - Diesel
  • Dimensions
    • Height - Without Trailer - 73 in / 1856 mm
    • Length - Without Trailer - 128.4 in / 3261 mm
    • Width - Without Trailer - 48.9 in / 1243 mm
    • Weight with Lube Oil and Coolant, Without Trailer - 5167 lb / 2344 kg
  • Fuel Consumption
    • 100% Load 60Hz - 6.4 gal/hr / 24.2 l/hr
    • 75% Load 60Hz - 4.8 gal/hr / 18.3 l/hr
    • 50% Load 60Hz - 3.4 gal/hr / 12.9 l/hr
    • 100% Load 60Hz - 2 gal/hr / 7.6 l/hr
  • Noise rating (with enclosure)
    • Sound Power @ 7 meters (23 feet) @ Prime Rating - 68.7 dB(A)
  • Standard Equipment

    • cat c4.4 diesel engine
      • Heavy-duty.
        Turbocharged.
        After treatment
    • generator
      • LC3114F Frame
    • control panel
      • XQCP dgital set mounted controller
    • cat connect remote monitoring
      • Provides package monitoring and management
    • cooling system
      • Package mounted radiator with vertical air discharge.
        Filled from factory
    • charging / starting system
      • 12V heavy duty starting motor and charging alternator c/w battery isolator
    • fuel system
      • 24 hour dual wall fuel tank with 3 way directional valve for external supply
    • air filter
      • Cyclonic/paper with dust cup and service indicator
    • distribution
      • Single, robust enclosure for controls and distribution c/w 4 pole circuit breaker and safety cut off
    • structure
      • Heavy Duty steel base frame with integral fuel tank.
        Lifting frame and 4 point lift.
        base frame is wider than enclosure to protect generator set during transportation
    • enclosure
      • Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance
    • exhaust
      • Integrated spark arresting silencer
    • lube oil
      • On engine primary and secondary oil filters. Filled from factory
    • general
      • Factory tested and inspected

    Optional Equipment

    • kit
      • Cold Weather Kit