ATC-300+ CONTROLLER

ATC-300+ CONTROLLER

ATC-300+ CONTROLLER

ATC-300+ CONTROLLER

The ATC-300+ is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels. The ATC-300+ Controller provides programmed flexibility to address the needs of any system. It operates from all system voltages between 120 to 600V, single-phase and three-phase at 50 or 60 Hz. In addition, a period of no control power is provided. The controller monitors the condition of the three-phase line-to-line voltage and frequency of Source 1 and Source 2 power sources and can be programmed for single-phase operation. The ATC-300+ Controller provides the intelligence to ensure that the ATS operates properly through a series of programmed sensing and timing functions.

Rating Range

120 to 600V, single phase and three phase @ 50/60 Hz

Transfer Type

Switch application dependent

Switch Type

Switch application dependent
  • Specifications
  • Overview
    • Long Name -ATC-300+ CONTROLLER
    • Name -ATC-300+ CONTROLLER
    • Brand -Caterpillar
    • Status -Current
  • Technical Summary
    • Rating Range - 120 to 600V, single phase and three phase @ 50/60 Hz
    • Transfer Type - Switch application dependent
    • Switch Type - Switch application dependent
  • ATC Controller Specifications
    • Input Control Voltage - 65 to 145 Vac 50/60 hZ
    • Voltage Measurements of Utility - Source 1 VAB Source 2 VAB<br>Source 1 VAC Source 2 VBC<br>Source 1 VCA Source 2 VCA
    • Voltage Measurement Range - 0 to 790 VAC rms (50/60 Hz)
    • Voltage Measurement Accuracy - +/-2% of nominal input voltage
    • Frequency Measurements Of - Source 1 and Source 2
    • Frequency Measurement Range - 40 Hz to 70 Hz
    • Frequency Measurement Accuracy - +/- 0.1 Hz
    • Undervoltage Dropout - 50% to 90% of nominal voltage
    • Undervoltage Pickup - (Dropout +2%) to 99% of the nominal system voltage
    • Underfrequency Dropout Range - 90 to 97% of the nominal system frequency
    • Underfrequency Pickup Range - (Dropout +1 Hz) to 99% of the nominal system frequency
    • Overfrequency Dropout Range - 103 to 110% of the nominal system frequency
    • Overfrequency Pickup Range - 101% to (dropout - 1 Hz) of the nominal system frequency
    • Operating Temperature Range - -20 to 70 degree C (-4 to +158 degree F)
    • Storage Temperature Range - -30 to 85 degree C (-22 to +185 degree F)
    • Operating Humidity - 0 to 95% relative humidity (noncondensing)
    • Operating Environment - Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons
    • Generator Start Relay - 5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load
    • K1, K2 Relays - <br>10A, 1-3 hp @ 250 Vac</br><br>10A@30 Vdc</br>
    • Applicable Testing - UL-recognized component<br>Meets intent of UL 991 & UL 1008<br>Meets IEC 1000-4-2, 1000-4-3, 1000-4-4
    • Applicable Testing Continued - 1000-4-5, 1000-4-6, 1000-4-11<br>CISPR 11, Class A<br>FCC Part 15, Class A<br>CSS 22.2-178
    • Enclosure Compatibility - NEMA 1, NEMA 3R and NEMA 12<br>UV-resistant ATC-300+ faceplate