3516C (60 Hz)
3516C Generator Set
3516C (60 HZ) 1650-2500 kW Diesel Generator models offer flexible packaging options to work with your spatial requirements and environmental conditions.
3516C (60 Hz)
3516C (60 Hz)
Producing reliable power from 1825 to 2500 ekW at 60 Hz, our 3516C diesel generator sets are made to meet your mission critical, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. The 3516C generator sets are U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 Nonroad Equivalent Emission Standards), Low Fuel Consumption certified.
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Electric Power
- Specifications
- Standard / Optional Features
- Long Name -3516C Generator Set
- Name -3516C (60 Hz)
- Brand -Cat
- Status -Current
- Standby Rating - 2500/2250/2000 ekW
- Prime Power Rating - 2250/2045/1825 ekW
- Emissions/Fuel Strategy - U.S. EPA Cert., Tier 2
- Voltage - 380 to 13800 Volts
- Frequency - 60 Hz
- Speed - 1800 rpm
- Duty Cycle - Standby, Mission Critical, Prime, Continuous
- Maximum Rating - 2500 ekW
- Minimum Rating - 1650 ekW
- Engine Model - 3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel
- Bore - 6.69 in / 170 mm
- Stroke - 7.48 in / 190 mm
- Stroke - HD - 8.46 in / 215 mm
- Displacement - 4764.73 in / 78 l
- Compression Ratio - 14.7:1
- Aspiration - TA
- Fuel System - Electronic unit injection
- Governor Type - Adem™3
- Length - Minimum - 266.2 in / 6761 mm
- Length - Maximum - 276.3 in / 7019 mm
- Width - Minimum - 92.1 in / 2339 mm
- Width - Maximum - 92.1 in / 2339 mm
- Height - Minimum - 118 in / 2997 mm
- Height - Maximum - 118 in / 2997 mm
- Dry Weight - Genset (minimum) - 35880 lb / 16275 kg
- Dry Weight - Genset (maximum) - 38780 lb / 17590 kg
Standard Equipment
- air cleaner
- Single element with service indicator
- starting
- Heavy duty electric starter(s)
- cooling
- Standard Ambient Radiator
- crankcase ventilation system
- Non filtered crankcase ventilation
- mounting system
- Rails
- controller
- Cat ECS 100
- telematics
- Ethernet
- alternator
- Random wound
- Internal Excitation (IE)
- power termination
- Busbar
Optional Equipment
- air cleaner
- Dual element with service indicator
- starting
- Standard batteries
- Oversized batteries
- Battery charger - 10A
- Battery charger - 20A
- Battery charger - 40A
- Air starter(s)
- Jacket water heater
- cooling
- No Radiator
- High Ambient Radiator
- crankcase ventilation system
- Filtered crankcase ventilation
- Closed filtered crankcase ventilation
- muffler
- Industrial grade (15 dB)
- mounting system
- Rubber
- Spring vibration Isolators
- Seismic rated vibration isolators
- controller
- Cat ECS 200
- EMCP 4.4
- controller attachments
- Local annunciator module
- Remote annuciator module
- Expansion I/O module
- Remote monitoring software
- telematics
- Cellular
- extended service terms
- 2 year (Prime)
- 3 year
- 5 year
- 10 year
- extended service coverage
- Silver
- Gold
- Platinum
- Platinum plus
- alternator
- Form wound
- Permanent Magnet (PM) Excitation
- alternator temperature rise (over 40°c ambient)
- 80°C
- 105°C
- 125°C/130°C
- 150°C
- alternator output voltage
- 480V
- 600V
- 4160V
- 6300V
- 6600V
- 6900V
- 12470V
- 13200V
- 13800V
- alternator attachments
- Anti-condensation space heater
- Stator and bearing temperature monitoring and protection
- power termination
- Circuit breaker
- circuit breaker
- 1600A
- 2000A
- 2500A
- 3000A
- 3200A
- 4000A
- 5000A
- Electrically operated
- trip unit
- LSI
- LSI-G
- LSI-P
- LSIG-P
- ancilliary equipment
- Automatic transfer switch (ATS)
- Paralleling switchgear
- Paralleling controls
- certifications
- UL 2200
- IBC seismic certification
- HCAI/OSHPD OSP preapproved